Allen-Bradley / Rockwell · SLC 500 · PLC CPU · SLC 5/05 Ethernet processor
Allen-Bradley / Rockwell 1747-L552
Analysis reviewed: September 11, 2026
What should replace this part?
The documented replacement is CompactLogix 5380 platform (5069 family; no 1:1 catalog). This is a platform migration, not a drop-in swap.
Move to CompactLogix 5380 in stages — repair or retained I/O covers the changeover
- Rockwell discontinued the SLC 5/05 controller family on March 31, 2024.
- Rockwell's migration profile moves SLC 500 applications to CompactLogix 5380. It covers the platform, not your exact catalog, so the 5069 hardware still needs sizing.
- The 1747-AENTR adapter keeps your SLC I/O running as remote I/O, so you can switch processors without a single big shutdown.
Your options
What will need to change?
| Hardware | The 1746 chassis gives way to the 5069 platform. Replan power and capacity for the new rack. |
|---|---|
| Software | Move the program from RSLogix 500 to Studio 5000 Logix Designer and revalidate the application. |
| Wiring | Either rewire for the new I/O or use 1492 conversion hardware. The AENTR path keeps existing SLC I/O connected remotely instead. |
For anything not listed here, check the replacement manual against your existing configuration.
Need help confirming this replacement?
Send us the part number and current setup for 1747-L552. We'll help determine whether you need a replacement, repair, original-stock sourcing, or a migration.
Request a replacement reviewCan I still buy the original?
We did not verify current new-original stock for this exact part.
Lifecycle
Technical evidence
The recommendation above is based on the sources listed here. OEM source means the manufacturer published it; third-party source means a distributor, repair company or reseller states it. Confidence reflects how directly those sources support the recommendation: High — directly supported by manufacturer documentation. Medium — supported by family-level, secondary, or otherwise less-direct evidence. Low — limited or indirect evidence; verify independently before ordering.
OEM / manufacturer sources
Source excerpt“1747-AENTR enables CompactLogix/ControlLogix to control SLC I/O via EtherNet/IP”
Third-party sources
Source excerpt“Removed from sale March 31 2024; repair support committed through ~March 31 2031”
Limitation: Direction comes from Rockwell's platform-level migration profile, not an L552 catalog. Repair is quoted per request, so line up the quote early.
Related replacement analyses
- Allen-Bradley / Rockwell 1746-IB16 — Related SLC 500 I/O module.
- Allen-Bradley / Rockwell 1747-L553 — Related SLC 500 controller.
- Allen-Bradley / Rockwell 1785-L80B — Related PLC-5 controller.
- Allen-Bradley / Rockwell 1746-OB16 — Related SLC 500 I/O module.
- Allen-Bradley / Rockwell 1785-L60B — Related PLC-5 controller.
- Allen-Bradley / Rockwell 1746-IA16 — Related SLC 500 I/O module.
- Allen-Bradley / Rockwell 1785-L40B — Related PLC-5 controller.