Allen-Bradley / Rockwell · SLC 500 · PLC I/O module · 16-pt 24VDC source output SLC
Allen-Bradley / Rockwell 1746-OB16
Analysis reviewed: September 11, 2026
What should replace this part?
The verified replacement is 5069-OB16 + 1492-CM1746-M03. This is an engineering replacement, not a drop-in swap.
Replace with 5069-OB16 using the conversion cable and module
- Rockwell's conversion table maps the 1746-OB16 exactly to the 5069-OB16, with conversion module 1492-CM1746-M03.
- Rockwell removed the SLC 500 family from sale on March 31, 2024, so the spare pool is finite.
- The same conversion pattern covers the rest of the 1746 I/O family.
Your options
What will need to change?
| Hardware | The SLC chassis gives way to a Compact5000 (5069) chassis. |
|---|---|
| Wiring | The 1492-CM1746-M03 conversion module carries your field wiring across. Re-terminate at the new RTB. |
| Software | Move the project from RSLogix 500 to Studio 5000. |
For anything not listed here, check the replacement manual against your existing configuration.
Need help confirming this replacement?
Send us the part number and current setup for 1746-OB16. We'll help determine whether you need a replacement, repair, original-stock sourcing, or a migration.
Request a replacement reviewCan I still buy the original?
We did not verify current new-original stock for this exact part.
Lifecycle
Status: Discontinued (family)
Discontinuation date: March 31, 2024 (family; exact date unknown)
Technical evidence
The recommendation above is based on the sources listed here. OEM source means the manufacturer published it; third-party source means a distributor, repair company or reseller states it. Confidence reflects how directly those sources support the recommendation: High — directly supported by manufacturer documentation. Medium — supported by family-level, secondary, or otherwise less-direct evidence. Low — limited or indirect evidence; verify independently before ordering.
OEM / manufacturer sources
Source excerpt“Digital Outputs table p10 with explicit Column 1/2/3 instructions; wiring diagram 1492-CM1746-M03 p21”
Third-party sources
Source excerpt“Removed from sale March 31 2024; repair support committed through ~March 31 2031”
Limitation: The conversion row is exact, but the neighboring OB16E cell is ambiguous — do not apply this mapping to the OB16E. Confirm field-device support and repair coverage before ordering.
Related replacement analyses
- Allen-Bradley / Rockwell 1746-IB16 — Related SLC 500 I/O module.
- Allen-Bradley / Rockwell 1747-L553 — Related SLC 500 controller.
- Allen-Bradley / Rockwell 1771-IBD — Related PLC-5 I/O module.
- Allen-Bradley / Rockwell 1747-L552 — Related SLC 500 controller.
- Allen-Bradley / Rockwell 1746-IA16 — Related SLC 500 I/O module.