Allen-Bradley / Rockwell · SLC 500 · PLC I/O module · 16-pt 120VAC input SLC

Allen-Bradley / Rockwell 1746-IA16

Discontinued

Analysis reviewed: September 12, 2026

What should replace this part?

The verified replacement is 5069-IA16 + 1492-CM1746-M01. This is an engineering replacement, not a drop-in swap.

Swap to the 5069-IA16 with the M01 conversion module — the AC field wiring carries over

Your options

5069-IA16 + 1492-CM1746-M01 conversion module
The Compact5000 AC input module plus the conversion module that preserves the SLC field terminations. The program converts from RSLogix 500 to Studio 5000 alongside the hardware.
Repair the installed SLC module
Rockwell flags this catalog as repairable, so a failed module can bridge the changeover while the Compact5000 chassis is planned. Use the bridge for timing, not as the end state.

What will need to change?

HardwareThe SLC chassis leaves and a Compact5000 chassis with the 5069-IA16 takes its place. One distributor guide names a different conversion module, but two OEM documents agree on the M01.
WiringThe M01 conversion module keeps the existing 85-132VAC field terminations. Check each field device against the 5069 electrical specification before re-landing wires.
SoftwareRSLogix 500 gives way to Studio 5000. Convert the program and retest I/O mapping and timing on the bench before cutover.
I/OThe count and AC input class stay at 16 points, but the module now lives on Compact5000 instead of the SLC rack. Revisit input filtering and scan-time assumptions in the new platform.

For anything not listed here, check the replacement manual against your existing configuration.

Need help confirming this replacement?

Send us the part number and current setup for 1746-IA16. We'll help determine whether you need a replacement, repair, original-stock sourcing, or a migration.

Request a replacement review

Can I still buy the original?

RepairAvailable for this modelUsedNot confirmed for this exact modelRefurbishedNot confirmed for this exact model

Lifecycle

Status: Discontinued

Discontinuation date: November 24, 2022

Lifecycle source · rockwellautomation.com

Technical evidence

The recommendation above is based on the sources listed here. OEM source means the manufacturer published it; third-party source means a distributor, repair company or reseller states it. Confidence reflects how directly those sources support the recommendation: High — directly supported by manufacturer documentation. Medium — supported by family-level, secondary, or otherwise less-direct evidence. Low — limited or indirect evidence; verify independently before ordering.

OEM / manufacturer sources

OEM source Confidence: High Rockwell Automation (product page)
Rockwell's product page discontinues the SLC 16 Point AC Input Module as of November 24, 2022, under the Engineering Replacement category, and flags it repairable.
Source excerptas of November 24, 2022, the SLC 16 Point AC Input Module will be discontinued ... Replacement Category: Engineering Replacement
View source · Note: Exact catalog page, opened and read; 85-132VAC signal spec.
OEM source Confidence: High Rockwell Automation (SLC 500 hardware migration reference 1746-RM003) · 2022-01
Rockwell's SLC migration reference maps the 1746-IA16 to the 5069-IA16 with conversion module 1492-CM1746-M01.
Source excerpt1746-IA16 to 5069-IA16 ... Conversion Module Catalog Number ... 1492-CM1746-M01
View source · Note: OEM manual section; matches the distributor conversion listing.
OEM source Confidence: Medium Rockwell Automation (conversion instructions 1492-IN132)
Rockwell's conversion instructions repeat the 1746-IA16 to 5069-IA16 with 1492-CM1746-M01 row in the chassis conversion table.
Source excerptSLC500 IO Module Catalog Number (To be converted): 1746-IA16 5069-IA16 1492-CM1746-M01
View source · Note: OEM instruction sheet; second document behind the same row.

Limitation: The conversion-module question is settled at the OEM level (M01 in two documents), while one distributor guide says otherwise. Check firmware and Studio 5000 revision floors for the 5069 side before ordering.