Allen-Bradley / Rockwell · SLC 500 · PLC I/O module · 16-pt 120VAC input SLC
Allen-Bradley / Rockwell 1746-IA16
Analysis reviewed: September 12, 2026
What should replace this part?
The verified replacement is 5069-IA16 + 1492-CM1746-M01. This is an engineering replacement, not a drop-in swap.
Swap to the 5069-IA16 with the M01 conversion module — the AC field wiring carries over
- Rockwell's product page declares this module discontinued with an Engineering Replacement category.
- Two OEM conversion documents agree the 1746-IA16 maps to the 5069-IA16 with conversion module 1492-CM1746-M01.
- The OEM repairable flag buys time for planned racks, but the chassis still has to go.
Your options
What will need to change?
| Hardware | The SLC chassis leaves and a Compact5000 chassis with the 5069-IA16 takes its place. One distributor guide names a different conversion module, but two OEM documents agree on the M01. |
|---|---|
| Wiring | The M01 conversion module keeps the existing 85-132VAC field terminations. Check each field device against the 5069 electrical specification before re-landing wires. |
| Software | RSLogix 500 gives way to Studio 5000. Convert the program and retest I/O mapping and timing on the bench before cutover. |
| I/O | The count and AC input class stay at 16 points, but the module now lives on Compact5000 instead of the SLC rack. Revisit input filtering and scan-time assumptions in the new platform. |
For anything not listed here, check the replacement manual against your existing configuration.
Need help confirming this replacement?
Send us the part number and current setup for 1746-IA16. We'll help determine whether you need a replacement, repair, original-stock sourcing, or a migration.
Request a replacement reviewCan I still buy the original?
Lifecycle
Technical evidence
The recommendation above is based on the sources listed here. OEM source means the manufacturer published it; third-party source means a distributor, repair company or reseller states it. Confidence reflects how directly those sources support the recommendation: High — directly supported by manufacturer documentation. Medium — supported by family-level, secondary, or otherwise less-direct evidence. Low — limited or indirect evidence; verify independently before ordering.
OEM / manufacturer sources
Source excerpt“as of November 24, 2022, the SLC 16 Point AC Input Module will be discontinued ... Replacement Category: Engineering Replacement”
Source excerpt“1746-IA16 to 5069-IA16 ... Conversion Module Catalog Number ... 1492-CM1746-M01”
Source excerpt“SLC500 IO Module Catalog Number (To be converted): 1746-IA16 5069-IA16 1492-CM1746-M01”
Limitation: The conversion-module question is settled at the OEM level (M01 in two documents), while one distributor guide says otherwise. Check firmware and Studio 5000 revision floors for the 5069 side before ordering.
Related replacement analyses
- Allen-Bradley / Rockwell 1746-IB16 — Related SLC 500 I/O module.
- Allen-Bradley / Rockwell 1747-L553 — Related SLC 500 controller.
- Allen-Bradley / Rockwell 1771-IBD — Related PLC-5 I/O module.
- Allen-Bradley / Rockwell 1746-OB16 — Related SLC 500 I/O module.
- Allen-Bradley / Rockwell 1747-L552 — Related SLC 500 controller.