Mitsubishi Electric · FX2N · PLC CPU
Mitsubishi Electric FX2N-48MR-UA1/UL
What should replace this part?
- OEM table explicitly states N/A for FX2N-48MR-UA1/UL
- Closest FX5U equivalents use 24VDC inputs — not equivalent to 100VAC UA1 inputs
- OEM repair period ended 2019
Your options
Replacement analysis
Relationship: No defensible replacement found HIGH
Migration / engineering work required — not a drop-in. This is not presented as a drop-in replacement.
Analyst note: AUDIT-CONFIRMED HIGH negative. Explicit OEM N/A; UA1 100VAC-input has no FX5U equivalent.
What changes?
| I/O | 100VAC UA1 inputs have no equivalent; sensors and input wiring must be re-engineered. |
|---|---|
| Software | GX Developer project converts to GX Works3 for any modern FX platform. |
| Mounting | Dimensions differ; panel layout must be re-checked. |
Anything not listed here is unknown — the evidence does not establish it.
Can I still buy the original?
New-original availability is not claimed unless evidence supports it. Availability is never implied by the existence of a listing alone.
Lifecycle
Evidence
Every important claim traces to a source below. OEM source means the manufacturer published it; third-party source means a distributor, repair company or reseller states it; our analysis connects them — and is labeled as such.
OEM / manufacturer sources
Why you might be searching this
FX2N-UA1 fault; why does no FX5U cross exist, and what now?